<?xml version="1.0" encoding="UTF-8"?><!DOCTYPE article  PUBLIC "-//NLM//DTD Journal Publishing DTD v3.0 20080202//EN" "http://dtd.nlm.nih.gov/publishing/3.0/journalpublishing3.dtd"><article xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink" dtd-version="3.0" xml:lang="en" article-type="research article"><front><journal-meta><journal-id journal-id-type="publisher-id">TDET</journal-id><journal-title-group><journal-title>Transmission and Distribution Engineering and Technology</journal-title></journal-title-group><issn pub-type="epub">2325-1565</issn><publisher><publisher-name>Scientific Research Publishing</publisher-name></publisher></journal-meta><article-meta><article-id pub-id-type="doi">10.12677/TDET.2021.102002</article-id><article-id pub-id-type="publisher-id">TDET-46080</article-id><article-categories><subj-group subj-group-type="heading"><subject>TDET20210200000_33795381.pdf</subject></subj-group><subj-group subj-group-type="Discipline-v2"><subject>工程技术</subject></subj-group></article-categories><title-group><article-title>
 
 
  电力系统潮流分析的牛顿–拉夫逊法计算
  Newton-Raphson Method for Power Flow Analysis of Power System
 
</article-title></title-group><contrib-group><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>类</surname><given-names>杰</given-names></name><xref ref-type="aff" rid="aff2"><sup>2</sup></xref><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>白</surname><given-names>雪</given-names></name><xref ref-type="aff" rid="aff2"><sup>2</sup></xref><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>谢</surname><given-names>印忠</given-names></name><xref ref-type="aff" rid="aff2"><sup>2</sup></xref><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib></contrib-group><aff id="aff2"><addr-line>临沂大学，自动化与电气工程学院，山东 临沂</addr-line></aff><aff id="aff1"><addr-line>null</addr-line></aff><pub-date pub-type="epub"><day>28</day><month>10</month><year>2021</year></pub-date><volume>10</volume><issue>02</issue><fpage>9</fpage><lpage>17</lpage><permissions><copyright-statement>&#169; Copyright  2014 by authors and Scientific Research Publishing Inc. </copyright-statement><copyright-year>2014</copyright-year><license><license-p>This work is licensed under the Creative Commons Attribution International License (CC BY). http://creativecommons.org/licenses/by/4.0/</license-p></license></permissions><abstract><p>
 
 
  潮流计算主要是根据一个给定的电网架构、参数以及其它的条件而来确定一个电力系统的各个组成部分在其中的稳定运行状况参数。本文通过研究牛顿–拉夫逊法原理，将其引入潮流计算建立了电力系统模型与算法，然后以3机9节点为具体实例，应用牛顿–拉夫逊法程序计算，再利用Simulink仿真中自带电力系统模型计算，通过两种方法潮流计算结果一致，表明牛顿–拉夫逊法在处理潮流计算上结果良好。
   Power flow calculation is mainly based on a given grid architecture, parameters and other condi-tions to determine the stable operation parameters of various components of a power system. By studying the principle of Newton-Raphson method, this paper introduces it into power flow calcula-tion and establishes the power system model and algorithm. Then, taking three machines and nine nodes as a specific example, using the Newton-Raphson method’s program to calculate, and then using the power system model in Simulink simulation to calculate. The results of the two methods are consistent, which shows that the Newton-Raphson method has good results in dealing with the power flow calculation.
 
</p></abstract><kwd-group><kwd>潮流计算，牛顿–拉夫逊法，Simulink仿真, Power Flow Calculation</kwd><kwd> Newton-Raphson Method</kwd><kwd> Simulink Simulation</kwd></kwd-group></article-meta></front><body><sec id="s1"><title>摘要</title><p>潮流计算主要是根据一个给定的电网架构、参数以及其它的条件而来确定一个电力系统的各个组成部分在其中的稳定运行状况参数。本文通过研究牛顿–拉夫逊法原理，将其引入潮流计算建立了电力系统模型与算法，然后以3机9节点为具体实例，应用牛顿–拉夫逊法程序计算，再利用Simulink仿真中自带电力系统模型计算，通过两种方法潮流计算结果一致，表明牛顿–拉夫逊法在处理潮流计算上结果良好。</p></sec><sec id="s2"><title>关键词</title><p>潮流计算，牛顿–拉夫逊法，Simulink仿真</p></sec><sec id="s3"><title>Newton-Raphson Method for Power Flow Analysis of Power System<sup> </sup></title><p>Jie Lei, Xue Bai, Yinzhong Xie<sup>*</sup></p><p>School of Automation and Electrical Engineer, Linyi University, Linyi Shandong</p><p>Received: Sep. 20<sup>th</sup>, 2021; accepted: Oct. 20<sup>th</sup>, 2021; published: Oct. 28<sup>th</sup>, 2021</p></sec><sec id="s4"><title>ABSTRACT</title><p>Power flow calculation is mainly based on a given grid architecture, parameters and other conditions to determine the stable operation parameters of various components of a power system. By studying the principle of Newton-Raphson method, this paper introduces it into power flow calculation and establishes the power system model and algorithm. Then, taking three machines and nine nodes as a specific example, using the Newton-Raphson method’s program to calculate, and then using the power system model in Simulink simulation to calculate. The results of the two methods are consistent, which shows that the Newton-Raphson method has good results in dealing with the power flow calculation.</p><p>Keywords:Power Flow Calculation, Newton-Raphson Method, Simulink Simulation</p><disp-formula id="hanspub.46080-formula2"><graphic xlink:href="//html.hanspub.org/file/1-2550213x5_hanspub.png?20211028170312669"  xlink:type="simple"/></disp-formula><p>Copyright &#169; 2021 by author(s) and Hans Publishers Inc.</p><p>This work is licensed under the Creative Commons Attribution International License (CC BY 4.0).</p><p>http://creativecommons.org/licenses/by/4.0/</p><p><img src="//html.hanspub.org/file/1-2550213x6_hanspub.png?20211028170312669" /> <img src="//html.hanspub.org/file/1-2550213x7_hanspub.png?20211028170312669" /></p></sec><sec id="s5"><title>1. 引言</title><p>由于经济快速发展及能源危机的出现，微电网分布式发电技术的研究成为热点，清洁电力能源应用得到广泛发展，形成智能化多种供电平台，优化了电力资源配置结构，使供电更加便利和准确，同时使用电户更有自主选择权，但分布式电源的并入对电网中电能质量、继电保护等产生影响，多电源供电模式改变了原来的单电源辐射式网络，使得配电网络中各个节点电压和电流发生变化，如分布式电压、线路潮流、电网损耗率等；另外部分分布式电源具有不可控性，环境变化引起输出变化波动明显，为保证配电网安全、经济、优质运行，应对电网网络中电源、损耗、继电保护等进行计算和分析 [<xref ref-type="bibr" rid="hanspub.46080-ref1">1</xref>] [<xref ref-type="bibr" rid="hanspub.46080-ref2">2</xref>]。</p><p>配电网的特点就是闭环设计、开环运行，稳态运行时为辐射网络结构，用电负荷和输电线路出现故障时会出现短暂环网运行状态；配电网中电缆支路非常多，支路间用电量差异明显、相位角也变化较大；电网中PQ节点和PV节点数量不同潮流计算的方法分为支路法和节点法，支路法以支路电流或支路功率为状态变量，用直接或前推回代法写出状态方程并求解；节点法以节点电流或电压列出状态方程，利用牛顿法、高斯法求解。</p><p>在含有分布式发电、配电的电力系统中，传统的前推回代等以传统辐射状电网为基础的算法不再适用。分析求解中应用最广泛的就是潮流计算，小到一个变电站的正常运行，大到地区电力网络系统的供应，都应用了潮流计算。潮流计算一般将配电网中电源节点划分成不同类型，如PQ、PI、P(Q)V等，主要以PQ、PV型节点为主，不同类型节点计算方法不同，通常处理时都简化为这两种后计算，将功率方程由非线性逐步转换为线性 [<xref ref-type="bibr" rid="hanspub.46080-ref3">3</xref>]。利用牛顿–拉夫逊潮流计算的实质是对非线性方程求解，方法是将非线性方程进行多次迭代计算，线性化后转换为矩阵方程，利用对修正方程进行反复计算，求解潮流计算方程。</p></sec><sec id="s6"><title>2. 算法原理与实例分析</title><p>电网潮流计算的关键是建模，分布式发电、配电系统中通常以电力电子并网转换器、控制器、保护器等电路构成DG装置(分布式发电装置；Distributed Generation)，在潮流计算中，通常可把DG装置整体作为一个节点处理。下面以3机9节点的小电力系统为实例进行潮流分析。</p><sec id="s6_1"><title>2.1. 一个三机九节点算例</title><p>如图1所示为3机节点系统的电力系统结构示意图，在该系统中，以100 MVA为基准功率，计算得出发电机数据、输电线路和变压器数据、系统的负荷参数等信息，分别为表1、表2、表3中的数据。</p><p>图1. 3机9节点电力系统的结构示意图</p><table-wrap id="table1" ><label><xref ref-type="table" rid="table1">Table 1</xref></label><caption><title> Generator data of 3-machine 9-node syste</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >发电机</th><th align="center" valign="middle" >No. l</th><th align="center" valign="middle" >No. 2</th><th align="center" valign="middle" >No. 3</th></tr></thead><tr><td align="center" valign="middle" >母线号</td><td align="center" valign="middle" >B1</td><td align="center" valign="middle" >B2</td><td align="center" valign="middle" >B2</td></tr><tr><td align="center" valign="middle" >类型</td><td align="center" valign="middle" >Slack</td><td align="center" valign="middle" >PV</td><td align="center" valign="middle" >PV</td></tr><tr><td align="center" valign="middle" >母线电压</td><td align="center" valign="middle" >1.04</td><td align="center" valign="middle" >1.025</td><td align="center" valign="middle" >1.025</td></tr><tr><td align="center" valign="middle" >有功功率</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >1.63</td><td align="center" valign="middle" >0.85</td></tr></tbody></table></table-wrap><p>表1. 3机9节点系统发电机数据</p><table-wrap id="table2" ><label><xref ref-type="table" rid="table2">Table 2</xref></label><caption><title> Transmission line and transformer data of 3-machine 9-node syste</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >母线号</th><th align="center" valign="middle" >类型</th><th align="center" valign="middle" >R</th><th align="center" valign="middle" >X</th></tr></thead><tr><td align="center" valign="middle" >B<sub>1</sub>-B<sub>4</sub></td><td align="center" valign="middle" >变压器</td><td align="center" valign="middle" >0</td><td align="center" valign="middle" >0.0576</td></tr><tr><td align="center" valign="middle" >B<sub>2</sub>-B<sub>7</sub></td><td align="center" valign="middle" >变压器</td><td align="center" valign="middle" >0</td><td align="center" valign="middle" >0.0625</td></tr><tr><td align="center" valign="middle" >B<sub>3</sub>-B<sub>9</sub></td><td align="center" valign="middle" >变压器</td><td align="center" valign="middle" >0</td><td align="center" valign="middle" >0.0585</td></tr><tr><td align="center" valign="middle" >B<sub>4</sub>-B<sub>5</sub></td><td align="center" valign="middle" >输电线路</td><td align="center" valign="middle" >0.01</td><td align="center" valign="middle" >0.085</td></tr><tr><td align="center" valign="middle" >B<sub>4</sub>-B<sub>6</sub></td><td align="center" valign="middle" >输电线路</td><td align="center" valign="middle" >0.017</td><td align="center" valign="middle" >0.092</td></tr><tr><td align="center" valign="middle" >B<sub>5</sub>-B<sub>7</sub></td><td align="center" valign="middle" >输电线路</td><td align="center" valign="middle" >0.032</td><td align="center" valign="middle" >0.161</td></tr><tr><td align="center" valign="middle" >B<sub>6</sub>-B<sub>9</sub></td><td align="center" valign="middle" >输电线路</td><td align="center" valign="middle" >0.039</td><td align="center" valign="middle" >0.17</td></tr><tr><td align="center" valign="middle" >B<sub>7</sub>-B<sub>8</sub></td><td align="center" valign="middle" >输电线路</td><td align="center" valign="middle" >0.0085</td><td align="center" valign="middle" >0.072</td></tr><tr><td align="center" valign="middle" >B<sub>8</sub>-B<sub>9</sub></td><td align="center" valign="middle" >输电线路</td><td align="center" valign="middle" >0.0119</td><td align="center" valign="middle" >0.1008</td></tr></tbody></table></table-wrap><p>表2. 3机9节点系统的输电线路和变压器数据</p><table-wrap id="table3" ><label><xref ref-type="table" rid="table3">Table 3</xref></label><caption><title> Load parameters of a 3-machine 9-node syste</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >负荷号</th><th align="center" valign="middle" >母线号</th><th align="center" valign="middle" >有功功率</th><th align="center" valign="middle" >无功功率</th></tr></thead><tr><td align="center" valign="middle" >P<sub>LI</sub></td><td align="center" valign="middle" >B<sub>5</sub></td><td align="center" valign="middle" >1.25</td><td align="center" valign="middle" >0.5</td></tr><tr><td align="center" valign="middle" >P<sub>L2</sub></td><td align="center" valign="middle" >B<sub>6</sub></td><td align="center" valign="middle" >0.9</td><td align="center" valign="middle" >0.3</td></tr><tr><td align="center" valign="middle" >P<sub>L3</sub></td><td align="center" valign="middle" >B<sub>8</sub></td><td align="center" valign="middle" >1</td><td align="center" valign="middle" >0.35</td></tr></tbody></table></table-wrap><p>表3. 3机9节点系统的负荷参数</p></sec><sec id="s6_2"><title>2.2. 牛顿–拉夫逊法潮流计算原理</title><p>牛顿–拉夫逊法计算潮流实质为求解非线性方程，将非线性方程逐次反复转变为线性方程求解 [<xref ref-type="bibr" rid="hanspub.46080-ref4">4</xref>]，如非线性方程：</p><p>f ( χ 1 , χ 2 , ⋯ , χ n ) = 0 ( i = 1 , 2 , ⋯ , n ) (1)</p><p>设 χ ( 0 ) 为初始估计值， χ 在 χ ( 0 ) 附近，利用泰勒级数展开并忽略高阶项后得：</p><p>f ( χ ( 0 ) + Δ χ ( 0 ) ) = f ( χ ( 0 ) ) + f ′ ( χ ( 0 ) ) Δ χ ( 0 ) (2)</p><p>式中 Δ χ ( 0 ) 是 χ 的修正量，通过求解上式得：</p><p>Δ χ ( 0 ) = − [ f ′ ( χ ( 0 ) ) ] − 1 f ( χ ( 0 ) ) (3)</p><p>(3)式为第一次迭代得出的修正量，将 Δ χ ( 0 ) 和 χ ( 0 ) 相加后得到变量的改进值 χ ( 1 ) ，如(4)式：</p><p>χ ( 1 ) = χ ( 0 ) + Δ χ ( 0 ) (4)</p><p>之后继续重复上面的计算过程，因为 Δ χ ( 0 ) 是忽略高阶项得到的，所以改进值 χ ( 1 ) 也存在误差，可以通过连续迭代来接近真值，迭代公式为：</p><p>f ′ ( χ ( k ) ) Δ χ ( k ) = − f ( χ ( k ) ) (5)</p><p>如此推导至k次迭代，得：</p><p>χ ( k + 1 ) = χ ( k ) + Δ χ ( k ) (6)</p><p>由上面推导过程可以看出，牛顿法的实质就是利用反复迭代法进行修正方程，直到满足下式结束计算：</p><p>max { | f ( χ 1 ( k ) , χ 2 ( k ) , ⋯ , χ n ( k ) ) | } &lt; ε 1 (7)</p><p>式中 ε 1 为预先设定的较小正数。</p><p>牛顿–拉夫逊潮流计算对初值要求很高，初始敏感性强，在计算过程中需要选择合适的初始值，式中的 Δ χ 的值才能足够小，修正方程才能合适。如果初始值选择的不符合要求将会不收敛。</p></sec><sec id="s6_3"><title>2.3. 牛顿–拉夫逊潮流算法流程</title><p>牛顿–拉夫逊潮流算法具有收敛速度快的特点。运算时如果初值选择恰当，该算法将会平方性收敛。配电网系统在正常运行时，各节点之间电压都额定电压值比较接近，相位差也很小，通常计算在同一个网络中的各个节点时可以任务电压初值近似相等。一般迭代4、5次可以得到精确的解 [<xref ref-type="bibr" rid="hanspub.46080-ref5">5</xref>]，且该算法对病态系统也可以可靠收敛。由于每次迭代都形成新的雅克比矩阵，该算法运算量较大，可以利用MATLAB中模型编程进行。程序流程图如图2所示。</p></sec><sec id="s6_4"><title>2.4. 电网的参数求解</title><p>以求解变压器参数为例，分别列出变压器电阻 R T 、电抗 X T 、电纳 B T 、电导 G T 的参数方程：</p><p>R T = P K 1000 U N 2 S N 2 ， X T = U K % 100 U N 2 S N ， B T = I 0 % 100 S N U N 2 ， G T = P 0 1000 U N 2 (8)</p><p>式中 U N 为额定电压、 S N 为容量、 P K 为短路损耗、 U K 为短路压降、 I 0 % 为空载电流百分比、 P 0 为空载损耗，以上所有参数的单位均为有名单位。</p><p>图2. 牛顿–拉夫逊法潮流计算程序框图</p></sec><sec id="s6_5"><title>2.5. 通过导纳矩阵计算出结果</title><p>迭代次数越多，数据的结果精度越高，在经过三次迭代之后，得到电压标幺值和电压相角等数据。</p><p>各节点的电压大小为(节点号从小到大排序)：</p><p>各节点的电压相角为(节点号从小到大排序)：</p></sec></sec><sec id="s7"><title>3. 基于Simulink中电力系统潮流计算</title><sec id="s7_1"><title>3.1. 系统的搭建</title><p>在Simulink的SimPowerSystems中为用户提供了变压器、发电机、负载等电力系统元器件模型 [<xref ref-type="bibr" rid="hanspub.46080-ref6">6</xref>] [<xref ref-type="bibr" rid="hanspub.46080-ref7">7</xref>]，本文在进行Simulink仿真中，选择模块如表4所示。</p><table-wrap id="table4" ><label><xref ref-type="table" rid="table4">Table 4</xref></label><caption><title> Module selectio</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >模块</th><th align="center" valign="middle" >类型</th><th align="center" valign="middle" >联结方式</th></tr></thead><tr><td align="center" valign="middle" >发电机</td><td align="center" valign="middle" >Synchronous Machine pu Standard</td><td align="center" valign="middle" >定子绕组为星形联结</td></tr><tr><td align="center" valign="middle" >变压器</td><td align="center" valign="middle" >Three phase Transformer (Two Windings)</td><td align="center" valign="middle" >Y-Y联结</td></tr><tr><td align="center" valign="middle" >线路</td><td align="center" valign="middle" >Three Phase Series RLC Branch</td><td align="center" valign="middle" >-</td></tr><tr><td align="center" valign="middle" >负荷</td><td align="center" valign="middle" >Three-Phase Dynamic Load</td><td align="center" valign="middle" >-</td></tr></tbody></table></table-wrap><p>表4. 模块选择</p><p>选择好模块后，按照系统图搭建，3机9节点系统的结构示意图如图3所示。</p><p>图3. 3机9节点系统的仿真图</p></sec><sec id="s7_2"><title>3.2. 模块参数的计算及设置</title><p>1) 发电机模型参数设置</p><p>在Simulink仿真图中点击发电机模块，设置其额定功率为100 MVA，额定电压为11.5 kV、频率为50 Hz，不改变其他参数。</p><p>2) 变压器模型参数设置</p><p>设置变压器模块的低压侧额定容量电压分别为10.5 KV，高压侧额定容量电压分别为115 KV，在变压器T1、T2的仿真模型中，设置其额定容量均应成100 MVA。</p><p>3) 线路模型参数计算及设置</p><p>对于线路电阻、电感、电容的有名值，依据假设条件中的数据修改其数值。</p><p>4) 负荷模型参数设置</p><p>对于负载Load 1的参数配置方式，设置在初始电压下的有功和无功功率分别为125,000 KW、50,000 Kvar，初始输出电压(initial output voltage)在执行Powergui模块时会被自动地获取。</p></sec><sec id="s7_3"><title>3.3. 计算结果</title><p>在Powergui完成仿真模型中各个部分参数设置工作后，在仿真界面点击“更新潮流 (Update Load Flow)”按钮，就会出现仿真结果。从潮流计算的仿真结果可以归纳得到如下表5所示。</p><table-wrap id="table5" ><label><xref ref-type="table" rid="table5">Table 5</xref></label><caption><title> Simulink calculation result</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Block Name</th><th align="center" valign="middle" >V_LF (pu)</th><th align="center" valign="middle"  colspan="2"  >Vangle_LF (deg)</th><th align="center" valign="middle" >P_LF (MW)</th><th align="center" valign="middle" >Q_LF (Mvar)</th></tr></thead><tr><td align="center" valign="middle" >Load 1</td><td align="center" valign="middle"  colspan="2"  >0.9503</td><td align="center" valign="middle" >−4.14</td><td align="center" valign="middle" >125.00</td><td align="center" valign="middle" >50.00</td></tr><tr><td align="center" valign="middle" >Bus*11*</td><td align="center" valign="middle"  colspan="2"  >0.9954</td><td align="center" valign="middle" >−2.29</td><td align="center" valign="middle" >0.00</td><td align="center" valign="middle" >0.00</td></tr><tr><td align="center" valign="middle" >Load 2</td><td align="center" valign="middle"  colspan="2"  >0.9658</td><td align="center" valign="middle" >−3.72</td><td align="center" valign="middle" >90.00</td><td align="center" valign="middle" >30.00</td></tr><tr><td align="center" valign="middle" >Bus*13*</td><td align="center" valign="middle"  colspan="2"  >1.0036</td><td align="center" valign="middle" >2.13</td><td align="center" valign="middle" >0.00</td><td align="center" valign="middle" >0.00</td></tr><tr><td align="center" valign="middle" >G3</td><td align="center" valign="middle"  colspan="2"  >1.0250</td><td align="center" valign="middle" >4.89</td><td align="center" valign="middle" >85.00</td><td align="center" valign="middle" >38.91</td></tr><tr><td align="center" valign="middle" >Three-Phase Series RLC Load2</td><td align="center" valign="middle"  colspan="2"  >1.0250</td><td align="center" valign="middle" >4.86</td><td align="center" valign="middle" >0.00</td><td align="center" valign="middle" >0.00</td></tr><tr><td align="center" valign="middle" >G1</td><td align="center" valign="middle"  colspan="2"  >1.0400</td><td align="center" valign="middle" >0.00</td><td align="center" valign="middle" >72.56</td><td align="center" valign="middle" >81.48</td></tr><tr><td align="center" valign="middle" >Three-Phase Series RLC Load1</td><td align="center" valign="middle"  colspan="2"  >1.0400</td><td align="center" valign="middle" >0.00</td><td align="center" valign="middle" >0.00</td><td align="center" valign="middle" >0.00</td></tr><tr><td align="center" valign="middle" >G2</td><td align="center" valign="middle"  colspan="2"  >1.0250</td><td align="center" valign="middle" >9.68</td><td align="center" valign="middle" >163.00</td><td align="center" valign="middle" >53.00</td></tr><tr><td align="center" valign="middle" >Three-Phase Series RLC Load</td><td align="center" valign="middle"  colspan="2"  >1.0250</td><td align="center" valign="middle" >9.68</td><td align="center" valign="middle" >0.00</td><td align="center" valign="middle" >0.00</td></tr><tr><td align="center" valign="middle" >Load 3</td><td align="center" valign="middle"  colspan="2"  >0.9790</td><td align="center" valign="middle" >0.83</td><td align="center" valign="middle" >100.00</td><td align="center" valign="middle" >35.00</td></tr><tr><td align="center" valign="middle" >Bus*9*</td><td align="center" valign="middle"  colspan="2"  >0.9970</td><td align="center" valign="middle" >3.97</td><td align="center" valign="middle" >0.00</td><td align="center" valign="middle" >0.00</td></tr><tr><td align="center" valign="middle" ></td><td align="center" valign="middle" ></td><td align="center" valign="middle" ></td><td align="center" valign="middle" ></td><td align="center" valign="middle" ></td><td align="center" valign="middle" ></td></tr></tbody></table></table-wrap><p>表5. Simulink运算结果</p><p>将运算模型得出的数据进行整理，按照节点号从小到大的顺序排列各节点的电压标幺值和电压相角，得到如下数据分析。</p><p>对比图4与图5的实验结果可以发现，使用潮流计算分析的牛顿–拉夫逊法和Simulink仿真的各节点电压、相角基本稳定重合在一起，均对电力系统网络分解与分析有较为准确的求解。</p><p>图4. 各节点的电压标幺值对比</p><p>图5. 各节点的电压相角对比</p></sec><sec id="s7_4"><title>3.4. 对比分析</title><p>1) 求解过程的差异。Matlab平台编写潮流计算程序得出结果的过程是：对非线性方程求解，将非线性方程进行多次迭代计算，线性化后转换为矩阵方程，利用对修正方程进行反复计算，求解潮流计算方程来得到最后的数据结果；而Simulink是通过Powergui中模型搭建设置初始值，经过模型内部算法得到各个节点电压、相角等数据结果。</p><p>2) 数据分析的差异。在同样的数据填入电力系统模型下，Matlab程序利用矩阵可以有选择性地不填入发电机、变压器电抗电阻等数据；而在Powergui模型中，则需要填入较为具体及详细的参数，模型较为复杂，但是模型的搭建更加直观、更贴合实际生活。</p></sec></sec><sec id="s8"><title>4. 总结</title><p>本文先简单介绍了在含有分布式发电、配电的电力系统中，传统的前推回代等以传统辐射状电网为基础的算法不再适用，牛顿–拉夫逊法、快速解耦法、高斯–赛德尔法等潮流计算逐渐被广泛地应用。基于此，本文借助牛顿–拉夫逊法来研究潮流计算过程，然后以3机9节点机电力系统为例，分别在Simulink的Powergui模块中搭建仿真模型以及通过对潮流计算所需要的数学模型进行分析，建立潮流计算的基本方程，利用Matlab平台编写潮流计算程序。将两种实验结果进行对比，对比结果表明，电压、相角方面，Matlab平台编写程序的实验结果与Simulink中的Powergui模块仿真结果几乎一样。通过验证，将3机9节点系统延伸到更复杂的电力系统网络分析时，在通常情况下，其中任意一种方法均可以有效地使用。</p></sec><sec id="s9"><title>基金项目</title><p>临沂市科技局重点研发项目(No. 2015GG031)。</p></sec><sec id="s10"><title>文章引用</title><p>类 杰,白 雪,谢印忠. 电力系统潮流分析的牛顿–拉夫逊法计算Newton-Raphson Method for Power Flow Analysis of Power System[J]. 输配电工程与技术, 2021, 10(02): 9-17. https://doi.org/10.12677/TDET.2021.102002</p></sec><sec id="s11"><title>参考文献</title></sec></body><back><ref-list><title>References</title><ref id="hanspub.46080-ref1"><label>1</label><mixed-citation publication-type="other" xlink:type="simple">马为民, 吴方劼, 杨一鸣, 等. 柔性直流输电技术的现状及应用前景分析[J]. 高电压技术, 2014, 40(8): 2429-2439.</mixed-citation></ref><ref id="hanspub.46080-ref2"><label>2</label><mixed-citation publication-type="other" xlink:type="simple">瞿吉, 安允展, 董学育. 直流微电网协调控制策略研究[J]. 电工技术, 2018(24): 115-116.</mixed-citation></ref><ref id="hanspub.46080-ref3"><label>3</label><mixed-citation publication-type="other" xlink:type="simple">徐劲松, 宁玉琳, 杨永峰. 基于Matlab的电力系统PQ分解法潮流计算研究[J]. 电气传动自动化, 2011, 33(2): 10-16.</mixed-citation></ref><ref id="hanspub.46080-ref4"><label>4</label><mixed-citation publication-type="other" xlink:type="simple">张丽英. 对电力系统潮流计算的分析与研究[J]. 电子技术与软件工程, 2020(22): 221-223.</mixed-citation></ref><ref id="hanspub.46080-ref5"><label>5</label><mixed-citation publication-type="other" xlink:type="simple">张明锐, 杜志超, 王少波. 微网中下垂控制策略及参数选择研究[J]. 电工技术学报, 2014, 29(2): 136-144.</mixed-citation></ref><ref id="hanspub.46080-ref6"><label>6</label><mixed-citation publication-type="other" xlink:type="simple">党常亮. Matlab/Simulink在“电力系统分析”教学中的应用[J]. 高教学刊, 2019(12): 102-104.</mixed-citation></ref><ref id="hanspub.46080-ref7"><label>7</label><mixed-citation publication-type="other" xlink:type="simple">李文勋, 秦凯强. 不同控制模式对直流网络潮流的影响[J]. 电工技术, 2020(23): 56-59.</mixed-citation></ref></ref-list></back></article>